BACnet B-ACDC (Access Control Door Controller) - C++ example

A minimal, copy-paste-friendly example showing how to implement the BACnet B-ACDC (Access Control Door Controller) device profile in C++ using the CAS BACnet Stack. It listens on BACnet/IP (UDP 47808), answers ReadProperty and WriteProperty requests, is discoverable via Who-Is / I-Am, and runs one commandable Access Door the way a door controller does: a client locks, unlocks or pulse-unlocks it, the door re-locks itself when the pulse time runs out, and it reports when the door is forced open or held open too long. The lock relay and door contact it drives are a Simulation; everything BACnet does with them is real.

Download a prebuilt binary (Windows and Linux x64) - or build it yourself, see Build below.

  • TUTORIAL.md - how to extend this example and how to review it for conformance. Read it when you start turning this into your own device.
  • docs/PICS.md - the Protocol Implementation Conformance Statement: every object, every property, and who answers it.

Versions: this document describes example v1.3.0, built and verified against CAS BACnet Stack 6.0.23 (6.x @ 69b6249f), at Protocol_Revision 30, with the vendored common/ helper at v3.5.0. Running the example prints all three - if what it prints disagrees with this line, trust the program and check CHANGELOG.md.

The device this example creates

Device 389011  "Chipkin Example B-ACDC"   (Vendor 389 - Chipkin Automation Systems)
    │
    ├── Analog Input 1       "Bronze"      Present_Value  21.5    (REAL, degrees Celsius; read-only)
    ├── Binary Input 1       "Emerald"     Present_Value  active  (0 = inactive / 1 = active; read-only)
    ├── Multi-State Input 1  "Hot Pink"    Present_Value  1       (state, 1..3; read-only)
    ├── Access Door 1        "Cobalt"      Present_Value  lock    (commandable - lock / unlock / pulse; re-locks itself)
    └── Network Port 1       "Vermilion"   the BACnet/IP port     (required on every device)

The three sensor objects are read-only, exactly as in the B-SS example. The Access Door is the one object that makes this a B-ACDC: its Present_Value is not stored directly, but resolved by the stack from a 16-slot Priority_Array plus a Relinquish_Default of lock - a WriteProperty(Present_Value, value, priority) sets a slot, NULL relinquishes it, and the stack reports the highest-priority non-null slot (or Relinquish_Default) as the effective value. A fire-alarm system can command the door at a high priority and a badge reader at a low one, and BACnet decides who wins. Present_Value is a BACnetDoorValue: 0 = lock, 1 = unlock, 2 = pulseUnlock, 3 = extendedPulseUnlock.

The scenario: a door that locks itself again

What a B-ACDC is for, in one sentence: it locks a door, unlocks it when told to, and locks it again. This example does that against a Peer - any BACnet client: an access control panel, a fire-alarm interface, a commissioning tool, or the Python client in tests/:

  1. The Peer writes Present_Value = pulseUnlock at priority 8 (what an access panel sends when someone badges in). The lock relay opens: Lock_Status = unlocked, Secured_Status = unsecured, Current_Command_Priority = 8.
  2. Someone walks through: Door_Status = opened.
  3. After Door_Pulse_Time (3.0 s by default) the controller relinquishes priority 8 by itself - Priority_Array[8] reads NULL, Present_Value falls back to lock, the relay locks. That is clause 12.26.16 of ANSI/ASHRAE 135-2024: the Present_Value "shall be automatically relinquished at the priority that established the PULSE_UNLOCK command". extendedPulseUnlock does the same on Door_Extended_Pulse_Time.
  4. Failure Mode - held open. If the door is still open Door_Open_Too_Long_Time after it re-locked, Door_Alarm_State reads doorOpenTooLong (12.26.19). Shut it and it returns to normal.
  5. Failure Mode - forced open. If the door opens while it is commanded lock - nobody was let in - Door_Alarm_State reads forcedOpen until it shuts.

A pulse written below a higher-priority command (a fire-alarm unlock at priority 5, say) is acknowledged and relinquished at once, as 12.26.4 requires; a pulse above one wins while it runs and then hands the door back to it. Every one of these steps is printed on the console as it happens.

The door does not send event notifications about its alarms: event reporting is optional for a B-ACDC, and a door controller that reports access events is a B-ACC / B-AACC. The alarm is in Door_Alarm_State for anyone who reads it.

The door Simulation

A real door controller has a lock relay (a GPIO output driving the strike or maglock) and a door-position contact (a reed switch on a GPIO input). This example has neither, so it simulates them - non-BACnet scaffolding, outside the BACnet Surface, in section 1b of main.cpp:

  • the lock relay follows the commanded Present_Value (open for unlock / pulseUnlock / extendedPulseUnlock), and is what Lock_Status reports;
  • the door contact is moved from the keyboard - o opens and shuts the door, f forces it open - and is what Door_Status reports;
  • p is a badge reader wired to the controller: a local pulseUnlock at priority 8, the same command an access panel would send over BACnet.

To port the example to hardware, replace the relay and contact variables with your GPIO and keep everything else. A client can also simulate the door over BACnet, the standard way: write Out_Of_Service = TRUE and Door_Status, Lock_Status and Door_Alarm_State become writable, and the alarm logic responds to written values "as if those changes had occurred to the physical door" (12.26.9). The Wire Tests use exactly that.

What this example supports

The example implements exactly the capabilities below - and nothing more, which is the point of a profile example.

BIBBs (BACnet Interoperability Building Blocks)

BIBB Description Supported
DS-RP-B Data Sharing - ReadProperty - B ✅
DS-WP-B Data Sharing - WriteProperty - B ✅
DS-ACAD-B Data Sharing - Access Control Access Door - B (the profile's defining BIBB) ✅
DM-DDB-B Device Management - Dynamic Device Binding - B ✅
DM-DOB-B Device Management - Dynamic Object Binding - B ✅

Deliberately not included - a B-ACDC does not require them, so a faithful profile example leaves them out: ReadPropertyMultiple, SubscribeCOV, alarms and events, scheduling, trending, and DeviceCommunicationControl. A door controller that also reports access events is a B-ACC / B-AACC - a different profile with its own example.

Services (executed / B-side)

Service Notes
ReadProperty Responds to property reads (DS-RP-B).
WriteProperty Accepts a door command into the Priority_Array, the door's three timing properties, and Out_Of_Service (DS-WP-B).
Who-Is / I-Am Answers Who-Is with I-Am, and broadcasts an I-Am on start-up (DM-DDB-B).
Who-Has / I-Have Answers Who-Has with I-Have (DM-DOB-B).

Object types

Object type Instance Name
Device 389011 Chipkin Example B-ACDC
Analog Input 1 Bronze
Binary Input 1 Emerald
Multi-State Input 1 Hot Pink
Access Door 1 Cobalt
Network Port 1 Vermilion

Every required property of every object, and who answers it, is in docs/PICS.md.

Requires the CAS BACnet Stack (licensed product)

This example builds against the CAS BACnet Stack, which is a commercial Chipkin product - it is not free or open source, and there is no public/trial build. The stack is referenced here as the private git submodule submodules/cas-bacnet-stack; you can only fetch and build it once you have a CAS BACnet Stack license and access to that repository.

To get the CAS BACnet Stack (and access to build this example), contact Chipkin: https://store.chipkin.com/services/stacks/bacnet-stack or sales@chipkin.com.

You do not need a stack licence to read this example, or to run a prebuilt release binary. The licence is what lets you build it - that is the part the stack submodule gates.

What's in this repository

This is a self-contained project. It ships:

  • main.cpp - the example device.
  • common/ - the shared helper (UDP, callbacks, CLI, keyboard) vendored in.
  • CMakeLists.txt - the build, the same on Windows, Linux, and macOS.
  • docs/PICS.md - the conformance statement.
  • tests/ - the Wire Tests (Python 3, standard library only), and wiretest/ - the series' shared Wiretest Harness they are written against (vendored, like common/).
  • submodules/cas-bacnet-stack/ - the CAS BACnet Stack as a git submodule (private; requires a license - see above). Its sources are compiled into the executable, so there is no library or DLL to build, ship, or install.

Prerequisites

  • A C++17 compiler (MSVC, GCC, or Clang).
  • CMake >= 3.15.
  • Git (to fetch the stack submodule).

Windows

Linux / macOS

  • Debian/Ubuntu: sudo apt install build-essential cmake git
  • macOS: xcode-select --install and brew install cmake

Build

CMake only, and the same two commands on every platform:

git clone --recursive https://github.com/chipkin/BACnetProfileExample-B-ACDC-CPP.git
cd BACnetProfileExample-B-ACDC-CPP

cmake -B build -S .
cmake --build build --config Release

Already cloned without --recursive? Run git submodule update --init --recursive first - the build needs the stack submodule.

The first build takes a few minutes - it compiles the entire CAS BACnet Stack (~600 source files) into the executable. Rebuilds after that are incremental and take seconds.

If your CAS BACnet Stack lives somewhere other than the bundled submodule, point CMake at it: cmake -B build -S . -D CAS_STACK_DIR=/path/to/cas-bacnet-stack.

Run

# Linux / macOS
./build/BACnetExampleBACDC

# Windows
.\build\Release\BACnetExampleBACDC.exe

Expected output:

BACnet B-ACDC (Access Control Door Controller) Example - C++ v1.3.0
CAS BACnet Stack version: 6.0.23.0
Common helper (common/) version: 3.5.0
FYI: Listening for BACnet/IP on UDP port 47808 (Network Port 1).
TX 21 bytes to 192.168.3.255:47808 (broadcast) (Network Port 1) - Unconfirmed: I-Am
FYI: Device 389011 ("Chipkin Example B-ACDC") ready. Vendor ID 389. Press 'h' for help.
FYI: Access Door 1 (Cobalt) starts lock, door shut. WriteProperty its Present_Value (0=lock, 1=unlock, 2=pulseUnlock, 3=extendedPulseUnlock) to command it.
FYI: the lock relay and door contact are a SIMULATION - keys o / f / p (h for help).

A badge (p) with the door opened (o) and left open prints:

Badge: Access Door 1 (Cobalt) <- pulseUnlock @ priority 8, re-locks in 3.0 s
Access Door 1 (Cobalt): Present_Value lock -> pulseUnlock
Simulation: lock relay energised (door unlocked) -> Lock_Status unlocked
Access Door 1 (Cobalt): Secured_Status unsecured
Simulation: door contact OPEN
Access Door 1 (Cobalt): Door_Status opened
Access Door 1 (Cobalt): pulseUnlock @ priority 8 expired - relinquished (12.26.16)
Access Door 1 (Cobalt): Present_Value pulseUnlock -> lock
Simulation: lock relay released (door locked) -> Lock_Status locked
Access Door 1 (Cobalt): Door_Alarm_State normal -> doorOpenTooLong

The TX line is the start-up I-Am the device broadcasts to announce itself. It goes to the local subnet broadcast address (here 192.168.3.255, computed from the Network Port's interface), not the global 255.255.255.255. As clients talk to the device you'll see RX ... bytes from ... and TX ... bytes to ... lines showing the traffic.

The device listens on UDP 47808 (BACnet/IP). Allow that port through your firewall. To use a different port, pass --port (see below).

A wall of red Error: lines at start-up is expected and is not your bug - it is the stack's own debug logging (the device hearing its own broadcast I-Am, and a one-time BACnet/SC UUID notice). TUTORIAL.md explains both.

Command-line options

Option Default Meaning
--port <n> 47808 UDP port to listen on (BACnet/IP).
--deviceID <n> 389011 The device's BACnet instance number (BACnet requires this to be configurable).
--deviceName <text> Chipkin Example B-ACDC The Device object's Object_Name, 1..255 bytes, no control characters. It must be unique across the BACnet internetwork, so give every unit its own (BACnet requires it to be configurable, like the instance). An invalid value prints a warning and keeps the default.
--xml off Print every received and sent BACnet message as an indented XML block instead of a one-line summary (very verbose; for protocol debugging).
--help, -h - Show usage and exit.
--version - Print the example, stack, and common/ helper versions, then exit.

Interactive commands

While the example runs, these keys are available:

Key Action
h Show the version information and this command list.
q Quit.
up arrow Increase Analog Input 1 (Bronze) by 1.1.
down arrow Decrease Analog Input 1 (Bronze) by 1.1.
o Simulation: open / shut the door (the door contact).
f Simulation: force the door open, whatever the lock is doing.
p Simulation: present a badge - pulseUnlock at priority 8.

Verify

Automated, on the wire - tests/ (Python 3 standard library only). One command starts the door controller and drives it from a Python client - the Peer:

python3 tests/run_wire_tests.py --exe build/BACnetExampleBACDC

They first discover the device the way a BACnet client does - every property every object lists must read as a value - then check that pulseUnlock and extendedPulseUnlock are relinquished at their own priority after their own times (Priority_Array slot NULL, Present_Value lock, relay locked), priority arbitration between a pulse and another command in both directions, refusal of a value that is not a BACnetDoorValue, and both Failure Modes - forced open and held open too long - plus the Simulation's own keys on Linux/macOS. Each check has been shown to fail with its feature removed (the table at the end of tests/README.md). A [KNOWN GAP] line is a stack defect, listed in TODO.md. CI runs them on Linux after the smoke test.

By hand - with a BACnet client such as the CAS BACnet Explorer:

  1. Discover - send a Who-Is. The device replies with I-Am from instance 389011 (vendor 389). It also broadcasts an I-Am at start-up.
  2. Browse the object model - the device shows six objects: the Device (Chipkin Example B-ACDC), the three sensors, the Access Door (Cobalt), and the Network Port (Vermilion). Reading the Device's Object_List returns all six.
  3. Read the Access Door - ReadProperty Access Door 1 -> Present_Value returns lock (nothing has commanded it, so it rests at Relinquish_Default).
  4. Command it - WriteProperty Access Door 1 Present_Value = 1 (unlock) at priority 8 -> read it back: unlock. Lock_Status now reads unlocked and Secured_Status reads unsecured.
  5. Confirm command arbitration - WriteProperty Present_Value = 0 (lock) at priority 1 -> the door reads lock: priority 1 outranks the priority-8 unlock, even though the unlock came later.
  6. Relinquish - WriteProperty Present_Value = NULL at priority 1 -> the door returns to unlock (slot 8 is still commanded). WriteProperty NULL at priority 8 too -> every slot is now null, so the door falls back to Relinquish_Default = lock.
  7. Confirm validation - WriteProperty Present_Value = 9 -> refused. (The stack at this pin answers Reject, not the value-out-of-range Error the standard names - see TODO.md.)
  8. Pulse - WriteProperty Present_Value = 2 (pulseUnlock) at priority 8, read Present_Value at once (pulseUnlock) and again after Door_Pulse_Time (3.0 s): lock, Priority_Array[8] NULL.
  9. The alarms - press o with the door locked: Door_Alarm_State reads forcedOpen; o again to shut it. Or badge (p), open (o) and wait Door_Open_Too_Long_Time (30 s) past the re-lock: doorOpenTooLong.

For a property-by-property review against the conformance statement, see TUTORIAL.md.

The BACnet profile example series

There is one example repository per standardized device profile in ASHRAE 135-2024 Annex L. An example marked ⛔ is blocked: the stack cannot yet perform that profile's function through its customer interface, and the example's README says what it does today. Pick the profile your device claims, then the language you build in. "Ask" means the example hasn't been built yet for that language - contact Chipkin if you need one.

Controllers (Annex L.4)

Profile C++ Node.js C# Rust Python Go
B-SS Smart Sensor B-SS-CPP B-SS-Node B-SS-CS B-SS-Rust B-SS-Python B-SS-Go
B-SA Smart Actuator B-SA-CPP Ask Ask Ask Ask Ask
B-ASC Application Specific Controller B-ASC-CPP B-ASC-Node Ask Ask Ask Ask
B-AAC Advanced Application Controller B-AAC-CPP Ask Ask Ask Ask Ask
B-BC Building Controller B-BC-CPP Ask Ask Ask Ask Ask

Life safety controllers (Annex L.5)

Profile C++ Node.js C# Rust Python Go
B-LSC Life Safety Controller B-LSC-CPP 🚧 Ask Ask Ask Ask Ask
B-ALSC Advanced Life Safety Controller B-ALSC-CPP Ask Ask Ask Ask Ask

Access control controllers (Annex L.6)

Profile C++ Node.js C# Rust Python Go
B-ACC Access Control Controller B-ACC-CPP Ask Ask Ask Ask Ask
B-AACC Advanced Access Control Controller B-AACC-CPP Ask Ask Ask Ask Ask

Lighting controllers (Annex L.11)

Profile C++ Node.js C# Rust Python Go
B-LD Lighting Device B-LD-CPP Ask Ask Ask Ask Ask
B-LS Lighting Supervisor B-LS-CPP Ask Ask Ask Ask Ask

Elevator controllers (Annex L.13)

Profile C++ Node.js C# Rust Python Go
B-EM Elevator Monitor B-EM-CPP Ask Ask Ask Ask Ask
B-EC Elevator Controller B-EC-CPP Ask Ask Ask Ask Ask
B-AEC Advanced Elevator Controller B-AEC-CPP Ask Ask Ask Ask Ask

Authentication and authorization (Annex L.14)

Profile C++ Node.js C# Rust Python Go
B-AS Authorization Server B-AS-CPP Ask Ask Ask Ask Ask

Miscellaneous (Annex L.7, combinable with any one family)

Profile C++ Node.js C# Rust Python Go
B-BBMD Broadcast Management Device B-BBMD-CPP Ask Ask Ask Ask Ask
B-ACDC Access Control Door Controller B-ACDC-CPP Ask Ask Ask Ask Ask
B-ACCR Access Control Credential Reader B-ACCR-CPP ⛔ blocked on stack #3934 Ask Ask Ask Ask Ask
B-RTR Router B-RTR-CPP Ask Ask Ask Ask Ask
B-GW Gateway B-GW-CPP Ask Ask Ask Ask Ask
B-DAP Device Address Proxy B-DAP-CPP ⛔ blocked on stack #2032 Ask Ask Ask Ask Ask
B-SCHUB BACnet/SC Hub B-SCHUB-CPP Ask Ask Ask Ask Ask
B-GENERAL General device (Annex L.8) (satisfied by every example above) — — — — —

Operator interfaces and workstations (Annex L.1–L.3, L.9–L.10, L.12)

Client-side profiles.

Profile C++ Node.js C# Rust Python Go
B-OD Operator Display B-OD-CPP Ask Ask Ask Ask Ask
B-OWS Operator Workstation planned — — — — —
B-AWS Advanced Operator Workstation planned — — — — —
B-XAWS Extended Advanced Operator Workstation planned — — — — —
B-LSAP Life Safety Annunciator Panel planned — — — — —
B-LSWS Life Safety Workstation planned — — — — —
B-ALSWS Advanced Life Safety Workstation planned — — — — —
B-ACSD Access Control Security Display planned — — — — —
B-ACWS Access Control Workstation planned — — — — —
B-AACWS Advanced Access Control Workstation planned — — — — —
B-LOD Lighting Operator Display planned — — — — —
B-ALWS Advanced Lighting Workstation planned — — — — —
B-LCS Lighting Control Station planned — — — — —
B-ALCS Advanced Lighting Control Station planned — — — — —
B-ED Elevator Display planned — — — — —
B-EWS Elevator Workstation planned — — — — —
B-AEWS Advanced Elevator Workstation planned — — — — —

🚧 = in progress. ⛔ = Blocked Example (blocked on the named stack gap). "Ask" = not yet built for that language; contact Chipkin if you need it. Profile definitions: ANSI/ASHRAE 135-2024 Annex L. BIBB definitions: Annex K. Get the stack: https://store.chipkin.com/services/stacks/bacnet-stack.

References

See also TUTORIAL.md, docs/PICS.md, CHANGELOG.md, and AGENTS.md.